Construction Techniques for Cold Storage Floor Insulation, Selection of Insulation Materials, and Key Considerations

2026-11-19 14:11:22
times

Construction Techniques for Cold Storage Floor Insulation, Selection of Insulation Materials, and Key Considerations

Ground insulation in large-scale cold-storage facilities constitutes the core component of the entire insulation system. The key design objectives are to minimize the loss of cooling capacity through the ground, prevent groundwater vapor from penetrating the insulation layer, and avoid soil frost heave and surface cracking under low-temperature conditions. At the same time, the insulation system must accommodate the operational requirements of large-scale cold-storage facilities, including high loads such as forklift traffic and the stacking of goods at elevated heights. The current industry-standard approach follows a construction sequence from the foundation to the surface layer; the structural details and parameters are as follows:

I. Standard Structural Levels (construction from bottom to top)

1. For foundation treatment, first remove the humus soil and miscellaneous fill soil from the construction area, then refill and compact the area in layers, ensuring that the compaction coefficient is not less than 0.94. If the groundwater level is more than 0.5 m below ground level, install drainage blind drains in the lower portion of the foundation in advance to divert the groundwater outside the reservoir, thereby preventing the foundation from being subjected to prolonged saturation by groundwater.

2. Pour a 100–150 mm thick layer of plain C15 concrete as the base course. Finish the surface by smoothing it until it is level and free of roughness, providing a continuous, even base surface for the upper vapor barrier layer and preventing sharp protrusions from puncturing the vapor barrier material.

3. As a key structural element that prevents groundwater vapor from penetrating the insulation layer, the vapor barrier should be installed on the high-temperature side of the insulation layer—the side facing the source of groundwater vapor. The conventional approach involves using two layers of 1.5 mm thick SBS-modified asphalt waterproof membrane, or a high-density polyethylene vapor barrier film (with a vapor permeability coefficient of ≤0.001 g/(m²·s·Pa)). During installation, the overlap width of the membrane shall be no less than 100 mm; at both convex and concave corners, two additional layers shall be applied. The vapor barrier must continuously overlap with the vertical vapor-barrier structure on the wall surface, forming a completely sealed vapor-barrier cavity with no leakage points.

4. The insulation layer serves as the core insulation structure and must be constructed using insulation materials with high compressive strength, low water absorption, and low-temperature resistance. The use of conventional insulation boards that are prone to water absorption and have low strength must be strictly prohibited.

o The commonly used material is Class B1 extruded polystyrene board specifically designed for cold-storage facilities, with high compressive strength (compressive strength: 350 kPa–800 kPa; thermal conductivity: ≤0.024–≤0.030 W/(m·K)).

o The insulation boards are installed in a staggered pattern, and the joints between the boards are filled with foam adhesive made from the same material to prevent the formation of thermal bridges.

5. A 20 mm thick leveling layer of 1:2.5 cement mortar shall be applied over the insulation layer. The surface shall be finished smooth and leveled to prevent cracks in the upper concrete surface layer caused by unevenness in the insulation boards.

6. The wear-resistant, load-bearing surface layer shall be cast as a 150–200 mm thick C30 reinforced concrete layer (C35 shall be used in areas subject to heavy traffic); it shall incorporate a Φ8@200 bidirectional reinforcing mesh to resist deformation caused by forklift traffic and the stacking of goods. At intervals of 6 m² across the surface layer, expansion joints shall be cut to a depth equal to one-third of the slab thickness. These joints shall be filled with low-temperature-resistant polysulfide sealant to prevent cold energy from escaping through the gaps. In warehouse areas where food-grade cleanliness requirements apply, a low-temperature-resistant epoxy wear-resistant coating may be applied to the surface of the layer.

II. Parameter Adjustment at Different Storage Temperatures

The thickness of the insulation layer must be dynamically adjusted based on the designed temperature inside the warehouse to prevent either excessive cooling capacity waste or insufficient insulation:

· Freshness preservation warehouse (high-temperature warehouse): -5°C to +15°C (typically around 0°C). It is primarily used to store fruits and vegetables, eggs, medicinal herbs, flowers, and similar products, with the aim of maintaining their freshness and preventing freezing. Some fruits and vegetables have more precise requirements: an XPS insulation layer thickness of 50–80 mm is sufficient to meet these requirements.

· Refrigerated warehouse (medium-temperature warehouse): -10°C to-5°C. Suitable for short-term storage or specific types of food, such as certain dairy products and chilled fresh meat. This temperature range falls between fresh-keeping conditions and deep-freezing conditions; the thickness of the XPS insulation layer should be 100–150 mm.

· Freeze storage facility (low-temperature storage facility): -25°C to-18°C. This is the most common temperature range for frozen storage, used for the long-term storage of meat, poultry, aquatic products, ice cream, and similar items. It effectively inhibits microbial growth and enzyme activity. The thickness of the XPS insulation layer is 150–200 mm.

· Low-temperature rapid-freezing warehouse: -25 to-35 °C, used for the rapid freezing of food. It is required that the center temperature of the food reach below-18 °C within a short period (typically within 30 minutes) in order to maximize the preservation of food quality; the thickness of the XPS insulation layer should be 200–250 mm.

· Ultra-low-temperature storage facility: -60°C to-45°C. It is used to store high-value marine products such as tuna, or special biological products and pharmaceuticals that require extremely low temperatures; the thickness of the XPS insulation layer should be 300–350 mm.

When selecting the compressive strength of XPS insulation boards, the appropriate compressive strength should be chosen based on the expected service loads in the cold storage facility during its later operation. For example, if forklifts are to operate inside the cold storage facility in the future, the compressive strength must not be less than 350 kPa; if high-level cargo stacking is planned, the compressive strength must not be less than 600 kPa or 800 kPa.

III. Special Measures for Preventing Freeze-Thaw Swelling in Low-Temperature Storage Facilities

When the warehouse temperature falls below –15 °C and the local foundation consists of frost-heave-prone soil (such as clay or silty clay), relying solely on a conventional insulation layer cannot prevent the underground soil temperature from dropping below 0 °C. The volume expansion of soil water as it freezes can cause the ground surface to crack. Two conventional methods are used to mitigate frost heave:

1. The overhead ventilation method involves pouring reinforced-concrete supports at intervals of 2–3 m on a concrete bedding layer. Each support is 300–500 mm high, and continuous ventilation ducts are left between the supports, connecting at both ends to the outdoor natural environment. Natural ventilation is used to keep the underground soil temperature above 0 °C. This method is the prevailing approach for large-scale low-temperature cold-storage facilities and involves low operation and maintenance costs.

2. Electrical heating method: When site conditions make overhead ventilation impractical, nickel-chromium alloy electric heating tubes may be pre-embedded above the vapor barrier and below the insulation layer, together with an automatic temperature-control system, to maintain the underground soil temperature at 3–5 °C. This method is suitable for small-scale cold-storage facilities or areas with excessively high groundwater levels.

IV. Key Construction Considerations

1. After the vapor barrier layer has been installed, a water retention test must be conducted. Only after confirming that there is no leakage should the insulation layer be installed, in order to prevent water vapor from penetrating the insulation layer and causing insulation failure.

2. The use of roof-grade low compressive-strength insulation boards (compressive strength ≤150 kPa) for floor insulation boards is strictly prohibited; otherwise, under prolonged heavy loading, these boards may be crushed, leading to floor settlement and failure of the insulation performance.

3. The ground insulation layer must be continuously connected to the wall insulation structure at the base of the wall; the upward projection height must be no less than 300 mm (with an uninterrupted insulation layer), to prevent the formation of a thermal bridge and condensation at the wall base.

 

 


Tags

Recently Viewed:

Related products

Related news

  • menu
底部联系

Tel:+86 27 83093866

XPS insulation board:+86 13255940828

EPS foam board:+86 13971297385

Production Address:No. 151 Yuanjiawan, Xin'andu Street, Dongxihu District, Wuhan City, Hubei Province, China

  • WeChat
    WeChat
  • Tiktok
    Tiktok
  • Copyright © Wuhan Fangyuan Insulation Materials Co., Ltd. All rights reserved record number:鄂ICP备案号06015299号 Mainly engaged inXPS board,XPS insulation board,XPS foam board, Welcome to inquire!
    Technical Support: Jakosns Network Disclaimers